Power Transformer
Espey Mfg. developed and manufactures this power distribution transformer used to supply electrical energy from a mobile military generator in rugged field conditions.
Electrical Specifications
- Rating: 115 volts 400 Hz MIL‑STD‑704 (Category B)
500 kVA, 2 minutes, emergency condition, limited duty cycle
400 kVA, 2 hrs in 24 hr period
200 kVA, 4 hrs in 12 hr period
100 kVA Continuous - Input: 8000 Volts Maximum
Primary: Delta connection
Voltage: 4160V
Frequency: 60 Hz ±2%
IEEE Std. 386 Loadbreak Interface: Integrated fuse and surge suppression - Output: Secondary: Wye connection, 4 Wire
Voltage: 480/277V
Regulation: 5.0% max at 400 kVA
Connection: Meltric PF 600 with integrated safety interlock & status
Circuit Breaker protected
Mechanical Specifications
- Unit weight: 5025 Lbs maximum
- Multiple lifting and transport options: Iso corners and fork lift options
- Enclosure: Ip55, carc painted steel
- Secondary disconnect: Circuit breaker
- Primary coolant and dielectric: Oil
Features
- Natural Convection Cooled
- Safety Interlocks
- IEEE Standard 386 Interface
- Interlocked Secondary Connector
- Integrated Thermal Protection
- Secondary Output Circuit Breaker
- Primary Fusing and Surge Arrestor
Click here for the PDF version.